Message Packet Formats
Chapter 5
5-36
Word Range Read
This is a read command whose starting address is either a word symbol, a
file symbol plus a word offset, or a block address. This starting address
must point to a word in a file. The function code is 1. A special case of
this command is the single-word read, where the number of bytes to read
is only two bytes (one word).
TNSDST SRC CMD 00 00FNC
0F 01
PACKET
OFFSET
TOTAL
TRANS
ASCII SYMBOL
(8 CHARS. MAX.)
W/F
00
TNSDST SRC CMD FNC
0F 01
PACKET
OFFSET
TOTAL
TRANS
PLC- 3 LOGICAL
ADDRESS
(2-51 Bytes)
SIZESTS
TNSSTSCMD
4F
SRCDST
TNSSTSCMD
4F
SRCDST EXT
STS
STS
DATA
— Max. of 244 Bytes
or 122 W
ords
Command
Format:
Reply Format:
(EXT STS Byte Is Optional)
B.
Format When Reporting an Error
A.
Format When Successful Execution
B.
Logical Address
A. W
ord Symbol Address
SIZE