Switch Settings
Appendix A
A2
Table A.B
Station Number (SW
2, SW3, SW
4)
A. First Digit (SW
2)
Switch
Digit 1 2
0
1
2
3
OFF
OFF
ON
ON
OFF
ON
OFF
ON
For a PLC network link, both of these switches must be OFF
.
B. Second and Third Digits (SW
3 and SW
4)
Switch
Digit 1 2 3
0
1
2
3
4
5
6
7
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Table A.C
Network Link Baud Rate (SW
5)
Switch
Baud Rate
1 2
Undefined
57,600
Undefined
Undefined
OFF
ON
ON
OFF
OFF
ON
OFF
ON
Table A.D
Asynchronous Link Baud Rate and Diagnostic Commands (SW
6)
Switch
Baud Rate
1 2 3
110
300
600
1,200
2,400
4,800
9,600
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
ON
Switch 4:
ON
Execute Diagnostic Command
OFF
Pass through Diagnostic Command