Rockwell Automation Publication 1788-UM057B-EN-P - September 2014 57
Diagnostics Chapter 4
PV Data Screen
If a field device has been configured and scheduled, its scheduled PV values are
displayed here. The name of the function block parameter that produces or
consumes the data is also displayed.
Table 6 - PV Status Colors
Click PV Data in the config tree to view the PV data for the device.
Oscilloscope Screen
The last packet received (good or bad) is displayed in the oscilloscope trace. Click
Oscilloscope in the config tree to view the last packet that is received for the
device.
PV Status Status Color
PVStatus 0x80 Green = good
0x40 PVStatus < 0x80 Orange = uncertain
PVStatus < 0x40 Red = bad