Rockwell Automation Publication 1788-UM057B-EN-P - September 2014 79
Field Device Block Configuration Examples Appendix C
24. Verify that the AO function block MODE_BLK > ACTUAL > Live
column displays Cas.
25. Set the CAS_IN (PV:O.1) value to 50%.
26. Verify that the BKCAL_OUT (PV:I.1) and OUT (PV:I.2) values change
as required (50% equals 12 mA at the OUT parameter).
The AO function block is now created, initialized, and operating correctly.