Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 47
Chapter
4
Configuring the I/O
This chapter provides instructions on how to configure a Rockwell Automation
ControlLogix or MicroLogix 1100/1400 controller to communicate with the
adapter and connected PowerFlex drive.
Using RSLinx Classic
Software
RSLinx Classic software, in all its variations (Lite, Gateway, OEM, and so forth),
is used to provide a communication link between the computer, network, and
controller. RSLinx Classic software requires its network-specific driver to be
configured before communication is established with network devices. To
configure the RSLinx driver, follow this procedure.
1. Start RSLinx Classic software and select Communications > Configure
Drivers to display the Configure Drivers screen.
2. From the Available Driver Types pull-down menu, choose EtherNet/IP
Driver.
3. Click Add New to display the Add New RSLinx Driver screen.
4. Use the default name or type a new name and click OK. The ‘Configure
driver:’ screen appears.
5. Depending on your application, select either the browse local or remote
subnet option.
6. Click OK.
Topic Page
Using RSLinx Classic Software
47
ControlLogix Controller Example 48
MicroLogix 1100/1400 Controller Example 68