20 Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013
Chapter 2 Installing the Adapter
The switch settings can be verified by viewing Diagnostic Device Item number 68
(page 111
) with any of the following drive configuration tools:
PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM
Connected Components Workbench software, version 1.02 or later
DriveExplorer software, version 6.01 or later
DriveExecutive software, version 5.01 or later
Also, you can use Parameter 37 - [Net Addr Src], a read-only parameter, to
verify the selected setting for Parameter 36 - [BOOTP].
Connecting the Adapter to
the Network
1. Remove power from the drive.
2. Remove the drive cover and lift up the drive HIM bezel to its open
position to access the drive control pod.
3. Use static control precautions.
4. Connect one end of an Ethernet cable to the network.
See Figure 2
for an example of wiring to an EtherNet/IP network.
Figure 2 - Connecting the Ethernet Cable to the Network
5. Route the other end of the Ethernet cable through the bottom of the
PowerFlex 755 drive, and insert the cable plug into the embedded
EtherNet/IP adapter mating socket (item 3 in Components
on page 11).
ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high
voltages that can cause injury or death. Remove power from the drive, and then
verify power has been discharged before connecting the embedded EtherNet/IP
adapter to the network.
Ethernet
Switch
Controller
(ControlLogix shown with
1756-ENBT Bridge)
PowerFlex 755 Drives
(each with embedded EtherNet/IP adapter)