Page 36 AutoMax ControlNet Module
Publication number DSMBCN-UM001B-EN-P February 2003
General
Status,
hex
Extended
Status,
hex
Explanation
01 0115 Product Type in the key segment did not match the
device
01 0116 Major or Minor Revision information in the key
segment did not match the device
01 0117 Invalid Connection Point. Could be the wrong
device type, device mismatches with scheduled
produced and consumed connections, etc.
01 0118 Invalid Configuration Format
01 0119 Connection request fails since there is no controlling
connection currently open.
01 011A Target Application cannot support any more
connections
01 0203 Connection cannot be closed since the connection
has timed out
01 0204 Unconnected Send timed out waiting for a response.
The destination device doesn’t exist (invalid
address, device turned off, etc.)
01 0205 Parameter Error in Unconnected Send Service
01 0206 Message too large for Unconnected message
service
01 0301 No buffer memory available
01 0302 Network Bandwidth not available for data
01 0303 No Tag filters available
01 0304 Not Configured to send real-time data
01 0311 Port specified in Path Segment Not Available
01 0312 Link Address specified in Path Segment Not
Available
01 0315 Invalid Segment Type or Segment Value in Path
01 0316 Path and Connection not equal in close
01 0317 Either Segment not present or Encoded Value in
Network Segment is invalid. The connection hasn’t
been scheduled. Run RS NetWorx.
01 0318 Link Address to Self Invalid
01 0319 Resources on Secondary Unavailable
02 n/a Connection Manager resources are unavailable to
handle service request