Rockwell-automation 1757-SWKIT400 Getting Started with ProcessLogix R4 Instrukcja Użytkownika Strona 18

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 24
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 17
18 Getting Started with ProcessLogix R400.0
Publication 1757-QS040A-EN-P - October 2001
Assigning the Control Module to the Controller Execution
Environment
To assign the Control Module for the PID loop to the CEE:
1. From Control Builder, select ToolsAssign.
2. On the Controller Assignments window, click the CMs/SCMs tab in the in the
Available Modules box.
3. Select FIC102 from the Available Modules box.
4. Select the CEE0101 from the CEE/Link box and click Assign.
The FIC102 module is displayed in the Assigned Modules box.
5. Close the Controller Assignments window.
Building the PID Loop
To develop the PID loop:
1. In the Project tab, open the Control Module by double-clicking FIC102.
2. Click the Library tab.
3. Display the available function blocks by clicking the + to the left of the
appropriate library in the tree display.
4. Click the desired block, then drag and drop it onto the your diagram.
5. Rename the block by double-clicking the block to bring up the Parameters
window.
6. Add the following function blocks to the Control Module:
In this library: Choose this function block: Rename:
DATAACQ DATAACQ DACA
IOCHANNEL AICHANNEL AI00
IOCHANNEL AOCHANNEL AO00
REGCTL PID PIDA
UTILITY NUMERIC NUMERIC
Przeglądanie stron 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 24

Komentarze do niniejszej Instrukcji

Brak uwag