Rockwell-automation 1761-NET-ENIW MicroLogix Ethernet Interface (ENI) Instrukcja Użytkownika Strona 133

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 132
1 Publication 1761-UM006E-EN-P - August 2005
Appendix
C
1761-NET-ENI/ENIW Performance
Considerations
Ethernet/IP Connections
The ENI/ENIW supports 6 concurrent TCP/IP connections: 2
incoming, 2 outgoing and 2 that can be allocated as incoming or
outgoing. Connection use can be viewed on the Diagnostics tab of the
ENI/ENIW web page (series D only).
Each TCP/IP connection simultaneously supports up to:
4 CIP connections
5 Unconnected sends
Packet Size Limitations
Each TCP/IP connection has its own DF1 queue. Each DF1 queue has
10 message buffers. The size of each message buffer is 580 bytes.
Using SLC-type reads, the following array sizes can be read over
Ethernet via the ENI/ENIW using the RSLinx OPC Test Client:
MicroLogix - 248 bytes of data
SLC 500 - 236 bytes of data
CompactLogix - 250 bytes of data
These limitations are due to serial port packet size limitations of the
respective controllers, not the ENI/ENIW.
Przeglądanie stron 132
1 2 ... 128 129 130 131 132 133 134 135 136 137 138 ... 143 144

Komentarze do niniejszej Instrukcji

Brak uwag