Block Transfer Write and Block Transfer Read Configurations for 2 Output/6 Input 1771-N Series Modules E–3
Publication 1771ĆUM127B-EN-P - December 2002
00010203040506070809101112131415
Word/Dec. Bit
00010203040506071011121314151617
Word/Octal Bit
49
Alarm
enable
Rate Alarm: Scaled Units per second
50 Filter Time Constant: 0.1 second units Alarm Deadband
51 Thermocouple Type 0 RTD Type 10 Ohm Offset: 0.01 Ohm units
Channel 8 Programming
52 Low Scale Value
53 High Scale Value
54 Low Alarm Value
55 High Alarm Value
56
Alarm
enable
Rate Alarm: Scaled Units per second
57 Filter Time Constant: 0.1 second units Alarm Deadband
58 Thermocouple Type 0 RTD Type 10 Ohm Offset: 0.01 Ohm units
Block Transfer Write Bit/Word Descriptions for 2 Output/6 Input
Modules
Word
Decimal Bit
(Octal Bit)
Definition
00-03 Constant = 0
Bits 04-07 Number of outputs = 0010
Word 0
Bits 08-13
(10-15)
Constant = 00 1000
Bits 14-15
(16-17)
Block transfer write type = 10
Word 1
Bits 00-15
(00-17)
First Output channel data
Word 2
Bits 00-15
(00-17)
Second Output channel data
Word 3 Bit 00
Verify. If this bit is set to 1, the module will compare its current
programming with the programming downloaded in the BTW. If
they are the same, it will verify good; if they are different, the
module will verify bad. In no case will any programming data in
the BTW be applied to the module.
Bit 01 Temperature scale. 0 = Celsius, 1 = Fahrenheit
Bit 02
BCD select. 1 = all values in BCD format.
0 = all values in 2's complement binary
Word 3 continued
Bits 03-14
(03-16)
Not used. Always 0