4–8 Configuring the Module
Publication 1771ĆUM127B-EN-P - December 2002
If both the low scale and high scale values are set to 0, the module
reports data in the default resolution as shown below.
Channel Type Data Format Temperature Scale Resolution
10V Output
Binary N/A 0.1mV/count
10V Output
BCD N/A 1mV/count
25mA Output
Binary N/A 0.1mA
25mA Output
BCD N/A 1mA
50mA Output
Binary N/A 0.1mA
50mA Output
BCD N/A 1mA
5V Input
Binary N/A 0.1mV
5V Input
BCD N/A 1mV
10V Input
Binary N/A 0.1mV
10V Input
BCD N/A 1mV
4 20mA Input
Binary N/A 0.1mA
4
Ć
20mA Input
BCD N/A 1mA
Binary Voltage Mode 0.01mV/count
BCD Voltage Mode 1mV/count
5/+55mV Input
Binary Celsius Mode 0.1
o
C/count
Ć
5/+55mV Input
BCD Celsius Mode 10
o
C/count
Binary Fahrenheit Mode 0.1
o
F/count
BCD Fahrenheit Mode 10
o
F/count
Binary Voltage Mode 0.01mV/count
BCD Voltage Mode 1mV/count
100mV Input
Binary Celsius Mode 0.1
o
C/count
100mV Input
BCD Celsius Mode 10
o
C/count
Binary Fahrenheit Mode 0.1
o
F/count
BCD Fahrenheit Mode 10
o
F/count
Binary Resistance Mode 0.1 Ohm/count
BCD Resistance Mode 1 Ohm/count
650 Ohm Input
Binary Celsius Mode 0.1
o
C/count
650 Ohm Input
BCD Celsius Mode 10
o
C/count
Binary Fahrenheit Mode 0.1
o
F/count
BCD Fahrenheit Mode 10
o
F/count