5–6 Module Status and Input Data
Publication 1771ĆUM127B-EN-P - December 2002
Output Status Data
Each output channel also has two words associated with it. The first
word contains low and high clamp, rate alarm, bad data, bad program
and bad calibration information for the processor. This is followed
by raw count data for that channel. If the module contains both input
and output channels, the output channel words would immediately
follow the header words.
Word/Dec. Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Channel 1 Status
4 Unused = 0 Bad
Calib
Bad
Prog
Bad
Data
Rate
Alarm
High
Clamp
Low
Clamp
Unused = 0
5 Channel 1 Raw Count sent to DAC
The above two words would be repeated for each output channel. For
example, if this module had two output channels, the following
words would be used.
Word/Dec. Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Channel 1 Status
4 Unused = 0 Bad
Calib
Bad
Prog
Bad
Data
Rate
Alarm
High
Clamp
Low
Clamp
Unused = 0
5 Channel 1 Raw Count sent to DAC
Channel 2 Status
6 Unused = 0 Bad
Calib
Bad
Prog
Bad
Data
Rate
Alarm
High
Clamp
Low
Clamp
Unused = 0
7 Channel 2 Raw Count sent to DAC