Appendix J
Publication 1771ĆUM127B-EN-P - December 2002
Block Transfer Write and Block
Transfer Read Configurations
for 5 Output/3 Input 1771ĆN
Series Modules
This appendix contains block transfer write and block transfer read
configurations and bit/word descriptions for 1771-N series modules
with five outputs and three inputs.
Block Transfer Write Configuration Block for 5 Output/3 Input
Modules
Word/Dec. Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
BTW word type Constant Number of outputs Constant
010 0 0 1 0 0 0 0 1 0 1 0 0 0 0
1 Channel 1 Output Data
2 Channel 2 Output Data
3 Channel 3 Output Data
4 Channel 4 Output Data
5 Channel 5 Output Data
6
CJ alarm
enable
Unused = 0
BCD
select
Temp
scale
Verify
7 RTS Sample Time: 1 millisecond units
Channel 1 Programming
8 Low Scale Value
9 High Scale Value
10 Low Clamp Value
11 High Clamp Value
12
Alarm
enable
Reset State 0 Maximum Ramp Rate, % of Full Scale per second
13 Reset Value
Channel 2 Programming
14 Low Scale Value
15 High Scale Value
16 Low Clamp Value
17 High Clamp Value
18
Alarm
enable
Reset State 0 Maximum Ramp Rate, % of Full Scale per second
What This Appendix
Contains