Publication 1794-UM064B-EN-P - May 2014
Additional HART Protocol Information 131
62 Read analog outputs 0 Analog output number
code for slot 0
0 Slot 0 analog output
number code
1 Slot 0 units code
2…5 Slot 0 level (F)
1 Analog output number
code for slot 1
6 Slot 1 analog output
number code
7 Slot 1 units code
8…11 Slot 1 level (F)
2 Analog output number
code for slot 2
12 Slot 2 analog output
number code
13 Slot 2 units code
14…17 Slot 2 level (F)
3 Analog output number
for slot 3
18 Slot 3 analog output
number code
19 Slot 3 units code
20…23 Slot 3 level (F)
63 Read analog output
information
0 Analog output number
code
0 Analog output number
code
1 Analog output alarm
select code
2 Analog output transfer
function code
3 Analog output range units
code
4…7 Analog output upper
range value
(F)
8…11 Analog output lower
range value
12…15 Analog output additional
damping value (seconds)
64 Write analog output
additional damping
value
0 Analog output number
code
As in command
1…4 Analog output additional
damping value (seconds)
(F)
65 Write analog output
range value
0 Analog output number
code
As in command
1 Analog output range
units code
2…5 Analog output upper
range value
(F)
6…9 Analog output lower
range value
Common Practice Commands
Command Data in Command Data in Reply
# Function Byte Data Type
(5)
Byte Data Type
(5)