Publication 1794-UM064B-EN-P - May 2014
38 Communicate With Your Module
1794-IRT8 Word/Bit Descriptions for Block Transfer Words
Word Dec. Bits
(Octal Bits)
Description
Write Word 0 00…02 Inpt Filter Cutoff Bits
Bit 02 01 00 Filter Time Constants – Actual filtering depends on the modules mode
of operation.
0 0 0 Hardware filtering only (default filtering).
00125 ms
010100 ms
011250 ms
100500 ms
1011 s
1102 s
1115 s
03…05 Reference Junction Used when input type is set to thermocouple and sensor mode is set to internal
compensation. Sets a fixed reference junction to compensate all thermocouple channels.
Bit 05 04 03 Reference Junction
0000 °C
00120 °C
01025 °C
01130 °C
10040 °C
10150 °C
11060 °C
11170 °C
06…07 Fault Mode Bits When a bit is set (1), fault mode is enabled for that channel. Bit 06 corresponds to
channels 0…3; bit 07 corresponds to channels 4…7.
0 = disabled
1 = enable wire-off detection
08…11
(10…13)
Data Format – Module defaults to -4000...10000 in millivolt mode, and 0...5000 in ohms mode with implied
decimal points (for example -40.00, 0.0 Ω ).
Bit 11 10 09 08 Data type for channels 0-7
0 0 0 0 °C (implies decimal point XXXX.X)
0 0 0 1 °F (implies decimal point XXXX.X)
0 0 1 0 °K (implies decimal point XXXX.X)
0 0 1 1 -32767...3267
01000...65535
0101...1111 not used
12…15
(14…17)
Not used