18 Communicate With Your Module
1794-IA8 – 8-point Discrete Input Module Image Table Mapping
0 1 1 Filter Time 3 2 ms
1 0 0 Filter Time 4 4 ms
1 0 1 Filter Time 5 8 ms
1 1 0 Filter Time 6 16 ms
1 1 1 Filter Time 7 32 ms
1794-IB10XOB6 Input Filter Times
Description Selected
Filter Time
02 01 00 Filter Time for Inputs 00…07
1794-IA8 Memory Map
Decimal Bit15 14 13 12 11 10 09 08 0706050403020100Size
Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 Read/Write Words
Not used
D7 D6 D5 D4 D3 D2 D1 D0 Read Word 0
Not used
Read Word 1
Not used
FT 00…07 Not used Write Word 0
Where: D = Input Data (D0 corresponds to input 0, D1 corresponds to input 1,and so on)
FT = Input Filter Time (FT 00…07 corresponds to inputs 0…7)
Filter
Time
1138
1794-IA8 Input Filter Times
Bits Description Maximum Filter Time
02 01 00 Filter Time for Inputs 00…15 (00…17) Off to On On to Off
0 0 0 Filter Time 0 (default) 8.6 ms 26.6 ms
0 0 1 Filter Time 1 9 ms 27 ms
0 1 0 Filter Time 2 10 ms 28 ms
0 1 1 Filter Time 3 12 ms 30 ms
1 0 0 Filter Time 4 17 ms 35 ms
1 0 1 Filter Time 5 26 ms 44 ms
1 1 0 Filter Time 6 43 ms 61 ms
1 1 1 Filter Time 7 78 ms 96 ms