Rockwell-automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual Instrukcja Użytkownika Strona 99

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 153
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 98
Publication 1794-UM064B-EN-P - May 2014
Configure the Adapter for Master/Slave Communication 87
The format of the adapter status word is defined in the following table:
The adapter expects the identifier area for each of the eight FLEX I/O slots to be
2 bytes. The DP input/output identifier and all specific DP identifiers (except
the empty module) are not supported.
The identifier byte and its format are described in the following illustration. This
byte is defined in Part 3 of the PROFIBUS Standard.
Adapter Status Word
Input Status Word
Bit Position Name Description
0
Address Change This bit is set when the Node Address switch is
changed since power up.
1…7
Reserved Sent as zeroes.
8…15
I/O Module Fault This bit is set when an error is detected in a slot
position (bits 0…7 refer to slots 1…8).
Output Status Word
Bit Position Name Description
0…15 Reserved sent as zeroes.
I/O Module Faults are caused by:
transmission errors on the FLEX I/O backplane
bad module
removed module
incorrect module inserted
Most Significant Bit
Bit Number
Consistency over
0 byte or word
1 whole length
length format
0 byte byte structure
1 word word structure
input/output
00 specific identifier formats
01 input
10 output
11 input-output
Length of data
00 1 byte resp. 1 word
15 16 byte resp. 16 words
76543210
Least Significant Bit
1160
Przeglądanie stron 98
1 2 ... 94 95 96 97 98 99 100 101 102 103 104 ... 152 153

Komentarze do niniejszej Instrukcji

Brak uwag