Publication 1797-6.5.3 - March 2006
Specifications A-11
1797-OE8H CENELEC I/O Entity Parameters
Signal output (+ to -) for ch 0 to ch 7 (terminals: 0 to 1; 4 to 5; 8 to 9; 12 to 13;
17 to 18; 21 to 22; 25 to 26; 29 to 30)
Keyswitch Position 4
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock, Operating
Shock, Non-Operating
Vibration
-20…+70 °C (-4…158 °F)
-40…+85 °C (-40…185 °F)
5…95% noncondensing
Tested to 15 g peak acceleration, 11 (+1)ms pulse width
Tested to 15 g peak acceleration, 11 (+1)ms pulse width
Tested 2 g @ 10…500 Hz per IEC 68-2-6
Agency Certification
CENELEC II (1) 2G EEx ia/ib IIB/IIC T4
II (1D) (2D)
Certificates
CENELEC DMT 00 ATEX E 042 X
Protection Group Allowed
Capacitance
Allowed
Inductance
Internal
Capacitance
Internal
Inductance
U
o
= 21.6V
I
o
= 92 mA
P
o
= 500 mW
EEx ia IIB 1.18 µF 1.18 µF 10 nF 0 mH