Publication 1797-6.5.3 - March 2006
Calibrate Your Module 5-19
1797-OE8H Calibration Item Byte Channel-Mask
The Calibration item byte channel-mask uses each bit of the byte to
correspond to one channel: where 1 is calibrate this channel and 0 is do not
calibrate this channel. The LSB corresponds to channel 0, for example, 0x03 >
channel 0 and 1 have to be calibrated. Only one channel can be calibrated at a
time. If there are more channels selected within the calibration commands, the
I/O module signals an error.
Table 5.14 1797-OE8HCalibration Item Byte Value Identifier List
Identifier (Decimal) Value Access Rule
0 Offset channel 0 Read/write
……
7 Offset channel 7
8 Gain channel 0
……
15 Gain channel 7
16 Offset current-read-back
channel 0
……
23 Offset current-read-back
channel 7
24 Gain current-read-back
channel 0
……
31 Gain current-read-back
channel 7
32 Offset voltage-read-back
channel 0
……
39 Offset voltage-read-back
channel 7
76543210
Calibrate channel 0
:
Calibrate channel 1
Calibrate channel 7