FLEX Ex HART Modules Network Messaging F-5
The actual channel to which actual contents are related.
Handle
This indicates the Handle of the response.
Response Error
In the following table, values 6 through 10 are communication errors.
Assembly Access Error
Chained data
Value Meaning
0…7 Channel of I/O module
0x20 FLEX Ex HART module itself
Value Meaning
0 No error
1 Timeout on HART loop
2 Invalid long frame address
3Locked
4 Request overflow
5 Response not available
6 Parity error
7 Overrun error
8 Framing error
9 Checksum error
10 Rx buffer overflow
11 No request
12…15 Reserved
Value Meaning
0 Access to assembly is invalid
1 Access not valid; take next assembly
(See next assembly pointer)
Value Meaning
0 No chained data in next assembly
1 Chained data in next assembly