Publication 1797-6.5.3 - March 2006
5-14 Calibrate Your Module
Table 5.9 1797-OE8H Calibration Command List
Calibration Command (Decimal)
Bits 0…5
Function
0 Reserved
1 Calibration command min scale
2 Calibration command max scale
3 Write measured min scale value (Current, uA)
4 Write measured min scale value (Voltage, uV)
5 Write measured max scale value (Current, uA)
6 Write measured max scale value (Voltage, uV)
7 Reserved
8 Set all calibration values to default
9 Set one specified calibration value to default
10…13
Reserved
(1)
14 Save calibration content to EEPROM
15…63 Reserved
(1)
Used during manufacture of the product. Do not use.