5-10 Calibrate Your Module
1797-IE8H Calibration Item Byte Value Identifier 49 (Status Mask Gain)
Each bit of the lower byte of this words corresponds to one channel. A logical
1 within the lower byte of the word means that this channel is calibrated
according to gain at room temperature. A 0 means that this channel is not
calibrating. In an attempt to write the upper byte of this word, write 0x00h. In
an attempt to read the upper byte of this word, 0x00h is given back.
15 14 13 12 11 10 9 8
Channel 0
76543210
Reserved Gain
Channel 1
:
Channel 7
Reserved
Reserved
: