Publication 1797-6.5.3 - March 2006
Calibrate Your Module 5-13
1797-OE8H Calibration Command Byte
The Calibration command byte uses the following format to write to the
module:
The Calibration command byte uses the following format to read from the
module:
76543210
Calibration command
Reserved (10
bin
must be written)
76543210
Last Calibration command mirrored back
Status of last written Calibration command
00
bin
= last written command executed/idle
01
bin
= error occurred during execution of last
command, command aborted
10
bin
= last written command pending
11
bin
= reserved