Using the I/O 5-23
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
PowerFlex 70, PowerFlex 700 with Standard Control, and PowerFlex 700H Drives
When using any of these products—which all contain INT (16-bit format)
data types—you will read from and write to the MSW data table address in
the controller.
Table 5.G Controller Data Table Addresses for:
PowerFlex 70 Drives with Standard or Enhanced Control
PowerFlex 700 Drives with Standard Control
PowerFlex 700H Drives
Data Table Address Description
N20:1 Logic Status (see Appendix D)
N20:2 Reserved
N20:3 Speed Feedback
N20:4 Value of parameter assigned to Parameter 310 [Data Out A1] LSW
N20:5 Value of parameter assigned to Parameter 310 [Data Out A1] MSW
N20:6 Value of parameter assigned to Parameter 311 [Data Out A2] LSW
N20:7 Value of parameter assigned to Parameter 311 [Data Out A2] MSW
N20:8 Value of parameter assigned to Parameter 312 [Data Out B1] LSW
N20:9 Value of parameter assigned to Parameter 312 [Data Out B1] MSW
N20:10 Value of parameter assigned to Parameter 313 [Data Out B2] LSW
N20:11 Value of parameter assigned to Parameter 313 [Data Out B2] MSW
N20:12 Value of parameter assigned to Parameter 314 [Data Out C1] LSW
N20:13 Value of parameter assigned to Parameter 314 [Data Out C1] MSW
N20:14 Value of parameter assigned to Parameter 315 [Data Out C2] LSW
N20:15 Value of parameter assigned to Parameter 315 [Data Out C2] MSW
N20:16 Value of parameter assigned to Parameter 316 [Data Out D1] LSW
N20:17 Value of parameter assigned to Parameter 316 [Data Out D1] MSW
N20:18 Value of parameter assigned to Parameter 317 [Data Out D2] LSW
N20:19 Value of parameter assigned to Parameter 317 [Data Out D2] MSW
N20:20 Logic Command (see Appendix
D)
N20:21 Reserved
N20:22 Speed Reference
N20:23 Value of parameter assigned to Parameter 300 [Data In A1] LSW
N20:24 Value of parameter assigned to Parameter 300 [Data In A1] MSW
N20:25 Value of parameter assigned to Parameter 301 [Data In A2] LSW
N20:26 Value of parameter assigned to Parameter 301 [Data In A2] MSW
N20:27 Value of parameter assigned to Parameter 302 [Data In B1] LSW
N20:28 Value of parameter assigned to Parameter 302 [Data In B1] MSW
N20:29 Value of parameter assigned to Parameter 303 [Data In B2] LSW
N20:30 Value of parameter assigned to Parameter 303 [Data In B2] MSW
N20:31 Value of parameter assigned to Parameter 304 [Data In C1] LSW
N20:32 Value of parameter assigned to Parameter 304 [Data In C1] MSW
N20:33 Value of parameter assigned to Parameter 305 [Data In C2] LSW
N20:34 Value of parameter assigned to Parameter 305 [Data In C2] MSW
N20:35 Value of parameter assigned to Parameter 306 [Data In D1] LSW
N20:36 Value of parameter assigned to Parameter 306 [Data In D1] MSW
N20:37 Value of parameter assigned to Parameter 307 [Data In D2] LSW
N20:38 Value of parameter assigned to Parameter 307 [Data In D2] MSW