Rockwell-automation 20-COMM-E PowerFlex EtherNet/IP Adapter Instrukcja Użytkownika Strona 250

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 296
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 249
C-16 EtherNet/IP Objects
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
DPI Parameter Object
Class Code
To access ‘Host Config’ parameters, use the HOST DPI Parameter Object
(Class code 0x9F).
Instances
The number of instances depends on the number of parameters in the
device. The total number of parameters can be read in Instance 0, Attribute
0.
Class Attributes
Hexadecimal Decimal
0x93 147
Instances (Hex.) (Dec.) Device Example Description
0x0000…0x3FFF 0…16383 Host 0 Class Attributes (Drive)
0x4000…0x43FF 16384…17407 Adapter 1 Drive Parameter 1 Attributes
0x4400…0x47FF 17408…18431 DPI Port 1 2 Drive Parameter 2 Attributes
0x4800…0x4BFF 18432…19455 DPI Port 2
0x4C00…0x4FFF 19456…20479 DPI Port 3 16384 Class Attributes (Adapter)
0x5000…0x53FF 20480…21503 DPI Port 4 16385 Adapter Parameter 1 Attributes
0x5400…0x57FF 21504…22527 DPI Port 5
0x5800…0x5BFF 22528…23551 DPI Port 6
0x5C00…0x5FFF
(1)
(1)
These instances are supported only when the adapter is used with a PowerFlex 750-Series drive.
23552…24575 DPI Port 7
0x6000…0x63FF
(1)
24576…25599 DPI Port 8
0x6400…0x67FF
(1)
25600…26623 DPI Port 9
0x6800…0x6BFF
(1)
26624…27647 DPI Port 10
0x6C00…0x6FFF
(1)
27648…28671 DPI Port 11
0x7000…0x73FF
(1)
28672…29695 DPI Port 12
0x7400…0x77FF
(1)
29696…30719 DPI Port 13
0x7800…0x7BFF
(1)
30720…31743 DPI Port 14
Attribute ID Access Rule Name Data Type Description
0 Get Number of Instances WORD Number of parameters in the device
1 Set Write Protect Password WORD 0 = Password disabled
n = Password
2 Set NVS Command Write BYTE 0 = No Operation
1 = Store values in active memory to NVS
2 = Load values in NVS to active memory
3 = Load default values to active memory
3 Get NVS Parameter Value Checksum WORD Checksum of all parameter values in a user set in NVS
4 Get NVS Link Value Checksum WORD Checksum of parameter links in a user set in NVS
5 Get First Accessible Parameter WORD First parameter available if parameters are protected by
passwords. A ‘0’ indicates all parameters are protected.
7 Get Class Revision WORD 2 = DPI
8 Get First Parameter Processing Error WORD The first parameter that has been written with a value
outside of its range. A ‘0’ indicates no errors.
9 Set Link Command BYTE 0 = No Operation
1 = Clear All Parameter Links (This does not clear links to
function blocks.)