20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
Appendix A
Specifications
This appendix presents the specifications for the adapter.
Communications
Electrical
Topic Page
Communications
A-1
Electrical A-1
Mechanical A-2
Environmental A-2
Regulatory Compliance A-2
Network
Protocol
Data Rates
EtherNet/IP
10 Mbps Full Duplex
10 Mbps Half Duplex
100 Mbps Full Duplex
100 Mbps Half Duplex
Connection Limits 30 TCP connections
16 simultaneous CIP connections including 1 exclusive-owner I/O
connection
The following activities use a CIP connection:
Class I I/O connections (for example, from a ControlLogix controller)
Explicit messaging where ‘connected’ is chosen (for example, in a
checkbox in RSLogix 5000 software)
DriveExecutive software connections to the drive
The following activities do not use a CIP connection:
Explicit messaging-based control using PCCC, or the Register or
Assembly objects, including the PLC-5, SLC 500, or MicroLogix 1100
controller examples in Chapter 4
Explicit messaging where ‘connected’ is not chosen, which is typically
the default
DriveExplorer software connections to the drive
Requested Packet
Interval (RPI)
5 ms minimum
Packet Rate Up to 400 total I/O packets per second (200 in and 200 out)
Drive
Protocol
Data Rates
DPI
125 kbps or 500 kbps
Consumption
Drive
Network
350 mA at 5V DC supplied by the host (drive or DPI External Comms Kit)
None