6-56 Using Explicit Messaging
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
MicroLogix 1100/1400 Controller Example Read Single Response Data
In this message example, we use the data table address in Figure 6.68
to
store the response value (0.13 amps) that was read from drive parameter 003
- [Output Current]. To determine the data type for the parameter and its
required scaling, see the specific drive documentation.
Figure 6.68 Example Read Single Response Data File
Figure 6.69 shows example ladder logic to correctly format the three
possible data types for read messages of different parameter types in the
MicroLogix 1100/1400 controller.
Figure 6.69 Example Ladder Logic to Format Parameter Data Types for Reads
For 16-bit Integer
Parameters – All
PowerFlex 7-Class
Drives
For 32-bit Integer
Parameters – All
PowerFlex 7-Class
Drives
For 32-bit REAL
(Floating Point)
Parameters –
PowerFlex 700S
and PowerFlex
750-Series Drives