Rockwell-automation 20-COMM-E PowerFlex EtherNet/IP Adapter Instrukcja Użytkownika Strona 167

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 296
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 166
Using Explicit Messaging 6-41
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
SLC 500 Controller Example Set Attribute Single Request Data
In this message example, we use the data table address in Figure 6.48
to
store the request value (10.0 sec.) that was written to drive parameter 140 -
[Accel Time 1]. To determine the data type for the parameter and its
required scaling, see the specific drive documentation.
Figure 6.48 Example Set Attribute SIngle Request Data File
Figure 6.49 shows example ladder logic to correctly format the three
possible data types for set messages of different parameter types in the SLC
500 controller.
Figure 6.49 Example Ladder Logic to Format Parameter Data Types for Sets
For 16-bit Integer
Parameters – All
PowerFlex 7-Class
Drives
For 32-bit Integer
Parameters – All
PowerFlex 7-Class
Drives
For 32-bit REAL
(Floating Point)
Parameters –
PowerFlex 700S
and PowerFlex
750-Series Drives
Przeglądanie stron 166
1 2 ... 162 163 164 165 166 167 168 169 170 171 172 ... 295 296

Komentarze do niniejszej Instrukcji

Brak uwag