Using Explicit Messaging 6-49
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
SLC 500 Controller – Formatting a Message to Write Multiple Parameters Using
Generic Get/Set Attribute Service
Figure 6.60 Custom Scattered Write Multiple Message Configuration Screens
The following table identifies the data that is required in each box to
configure a message to write multiple parameters.
General Tab Example Value Description
Size in Words
Data Table Address
Service
(1)
Service Code
Class
Instance
Attribute
15
(2)
N80:0
Custom
4C (Hex.)
93 or 9F (Hex.)
(3)
0 (Dec.)
0 (Dec.)
Number of words to be transferred. Each word size is a 16-bit integer.
An unused controller data table address containing the message
instruction. This address is the starting word of the source file.
Required for scattered messages.
Code for the requested service.
Class ID for the DPI Parameter Object.
Required for scattered messages.
Required for scattered messages.
MultiHop Tab Example Value Description
To Address 10.91.100.79 IP address of the adapter connected to the drive.
(1)
The default setting for Service is ‘Custom’, enabling entry of a Service Code not available from the Service pull-down menu. When
choosing a Service other than ‘Custom’ from the pull-down menu, an appropriate Hex. value is automatically assigned to the Service
Code box which is dimmed (unavailable).
(2)
In this example, we are writing to five parameters. Each parameter being written to requires three contiguous 16-bit words. Scattered
write messages always assume that every parameter being written to is a 32-bit integer, regardless of its actual data type. The data
structure format is the same as shown on page 6-42
. Maximum length is 66 words, which equates to 22 parameters. For parameter
numbering, see DPI Parameter Object
on page C-16 (Class code 0x93) or Host DPI Parameter Object on page C-30 (Class code
0x9F).
(3)
See Table 6.A on page 6-2 for limitations of PowerFlex 7-Class and PowerFlex 750-Series drives when using DPI Parameter Object
Class code 0x93 or Host DPI Parameter Object Class code 0x9F for explicit messaging.