134 Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013
Appendix C EtherNet/IP Objects
5 Get Data Type USINT 0xC2 = SINT (8-bits)
0xC3 = INT (16-bits)
0xC4 = DINT (32-bits)
0xC6 = USINT (8-bits)
0xC7 = UINT (16-bits)
0xCA = REAL (32-bits)
0xD2 = WORD (16-bits)
6 Get Data Size USINT
(3)
7 Get Parameter Name String SHORT_STRING
(3)
8 Get Units String SHORT_STRING
(3)
9 Get Help String SHORT_STRING
(3)
10 Get Minimum Value
(1) (3)
11 Get Maximum Value
(1) (3)
12 Get Default Value
(1) (3)
13 Get Scaling Multiplier UINT
(3)
14 Get Scaling Divisor UINT
(3)
15 Get Scaling Base UINT
(3)
16 Get Scaling Offset UINT
(3)
17 Get Multiplier Link UINT
(3)
18 Get Divisor Link UINT
(3)
19 Get Base Link UINT
(3)
20 Get Offset Link UINT
(3)
21 Get Decimal Precision USINT
(3)
(1) Access rule is defined in bit 4 of instance attribute 4. 0 = Get/Set, 1 = Get.
(2) Specified in descriptor, data type, and data size.
(3) Value varies based on parameter instance.
(4) Refer to the CIP Common specification for a description of the link path.
Attribute ID Access Rule Name Data Type Description