Chapter 2
Configuring the RediPANEL Module
2–5
Figure 2.2
DIP Switch Bank 1
Rack Address Settings for PLC-3, PLC-5 and SLC Processors
I
/
O
Rack
Address
Switch Settings
I
/
O
Rack
Switch Settings
I
/
O
Rack
Address
1
2 3 4 5 6
I
/
O
Rack
Address
1
2 3 4 5 6
00
on on on on on on 40 off on on on on on
01 on on on on on off 41 off on on on on off
02 on on on on off on 42 off on on on off on
03 on on on on off off 43 off on on on off off
04 on on on off on on 44 off on on off on on
05 on on on off on off 45 off on on off on off
06 on on on off off on 46 off on on off off on
07 on on on off off off 47 off on on off off off
10 on on off on on on 50 off on off on on on
11 on on off on on off 51 off on off on on off
12 on on off on off on 52 off on off on off on
13 on on off on off off 53 off on off on off off
14 on on off off on on 54 off on off off on on
15 on on off off on off 55 off on off off on off
16 on on off off off on 56 off on off off off on
17 on on off off off off 57 off on off off off off
20 on off on on on on 60 off off on on on on
21 on off on on on off 61 off off on on on off
22 on off on on off on 62 off off on on off on
23 on off on on off off 63 off off on on off off
24 on off on off on on 64 off off on off on on
25 on off on off on off 65 off off on off on off
26 on off on off off on 66 off off on off off on
27 on off on off off off 67 off off on off off off
30 on off off on on on 70 off off off on on on
31 on off off on on off 71 off off off on on off
32 on off off on off on 72 off off off on off on
33 on off off on off off 73 off off off on off off
34 on off off off on on 74 off off off off on on
35 on off off off on off 75 off off off off on off
36 on off off off off on 76 off off off off off on
37 on off off off off off
Rack 00 not valid with PLC-5s.
Specifying First I/O Group
Fi
rst
I
/
O
roup
Switch Settings
Fi
rst
I
/
O
Group
7
8
0 on on
2 on off
4 off on
6 off off