Chapter 4
Programming the RediPANEL Modules
4–17
Programming Example
The Sub I/O Scanner is in slot 1, module group 7 of the local I/O rack. The
Sub I/O Scanner is connected to three RediPANEL 16 button modules, each
configured for 1/4 rack.
• The Block Transfer Length is 14 (8 words for utility functions and 2
words for each of the 3 RediPANELS configured for 1/4 rack.
• Data File address for the block transfer read starts at N11:0. This means
that addresses for RediPANEL buttons start at N11:8.
The Data File for the block transfer write starts at N12:0. This means
addresses for the RediPANEL lamps start with N12:8.
Figure 4.6
PLC-5/15 and Sub I/O Scanner Programming Example
70123456
1771-I/O
(Local Rack 0)
PLC-
5/15
1771-I/O
(Remote 1)
1771
ASB
1771-I/O
(Remote 2)
1771
ASB
1771-I/O
(Remote 3)
1771
ASB
16 Button
RediPANEL
16 Button
RediPANEL
16 Button
RediPANEL
BLOCK TRNSFR READ
RACK 0
GROUP 7
MODULE 1
CONTROL BLOCK N10:0
DATA FILE N11:0
LENGTH 14
CONTINUOUS N
N10:0
]
/
[
15
N10:5
]
/
[
15
N10:5
]
/
[
15
N10:0
]
/
[
15
( ER )
( DN )
( ER )
( DN )
BTR
( EN )
( EN )
BLOCK TRNSFR WRITE
RACK 0
GROUP 7
MODULE 1
CONTROL BLOCK N10:5
DATA FILE N12:0
LENGTH 14
CONTINUOUS N
BTW
(Sub I/O Scanner)
1771-SN
01234567 01234567 01234567