PowerFlex® 6000 Medium Voltage Variable Frequency Drive
Commissioning Manual
Publication 6000-IN007A-EN-P
Commissioning Manual
Przeglądanie stron 0
1 2 3 4 5 6 ... 97 98

Podsumowanie treści

Strona 1 - Commissioning Manual

PowerFlex® 6000 Medium Voltage Variable Frequency Drive Commissioning ManualPublication 6000-IN007A-EN-PCommissioning Manual

Strona 2 - Important User Information

10 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014PrefaceNotes:

Strona 3 - Table of Contents

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 11Chapter 1IntroductionOverviewInformation contained in this chapter will assist in co

Strona 4

12 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 1 IntroductionProcess FlowchartsDocumentation and Application ReviewReview a

Strona 5

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 13Introduction Chapter 1• PLC Program: The PLC I/O processes control signals within th

Strona 6

14 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 1 IntroductionOn-site Verification of Electrical System One-line DiagramOnce

Strona 7 - Table 1 - Electrical Drawings

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 15Chapter 2Preparation and InspectionGather Required Tools and Test EquipmentHand Tool

Strona 8

16 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionLockout and tagout the input circuit breaker bef

Strona 9 - Additional Resources

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 17Preparation and Inspection Chapter 2Functional AssessmentAfter the components are vi

Strona 10

18 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionTable 3 - Inspect Drive Components ChecklistBypa

Strona 11 - Introduction

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 19Preparation and Inspection Chapter 2Table 4 - Functional Assessment ChecklistBypass

Strona 12 - Application Review

Important User InformationRead this document and the documents listed in the additional resources section about installation, configuration, and opera

Strona 13 - Review Drive Application

20 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionInterconnection ReviewThe interconnection checkl

Strona 14 - Chapter 1 Introduction

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 21Preparation and Inspection Chapter 2Installation ReviewPrior to commencing the commi

Strona 15 - Preparation and Inspection

22 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionElectrical Installation InspectionPower CablingT

Strona 16 - Inspect Drive Components

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 23Preparation and Inspection Chapter 2Incoming Line and Outgoing Motor cables must be

Strona 17 - Functional Assessment

24 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and Inspection2. Disconnect four 380V AC cables (a, b, c, and

Strona 18

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 25Preparation and Inspection Chapter 25. Switch the miniature circuit breakers in the

Strona 19

26 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and Inspection8. Disconnect the control cable of HECS.Figure 7

Strona 20 - Interconnection Review

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 27Preparation and Inspection Chapter 210. Remove the Analog Interface board and discon

Strona 21 - Installation Review

28 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and Inspection5. Disconnect the Insulation Meter and jumpers i

Strona 22 - Power Cabling

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 29Preparation and Inspection Chapter 2Final Steps before Equipment is Ready for Energi

Strona 23 - Drive Megger Check

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 3Table of ContentsPrefaceIntroduction. . . . . . . . . . . . . . . . . . . . . . . . .

Strona 24

30 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 2 Preparation and InspectionNotes:

Strona 25 - Figure 5 - Control Switches

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 31Chapter 3CommissioningIntroductionA number of activities are required before the Con

Strona 26 - Figure 8 - Back of HMI

32 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningControl System Check SetupSimulate Closed Input Circuit Break

Strona 27 - Connect the Insulation Meter

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 33Commissioning Chapter 3Figure 14 - LV Control CabinetFigure 15 - LV Panel in the Iso

Strona 28

34 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningFigure 16 - AC/DC Power SuppliesTable 8 - Energize Control Ci

Strona 29 - Energization

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 35Commissioning Chapter 3Control System CheckVerify Factory Default SettingsConfirm La

Strona 30

36 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press and confirm the Bypass Configuration matches one o

Strona 31 - Commissioning

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 37Commissioning Chapter 3The Select Local Control? dialog box appears.5. Select to c

Strona 32 - Control System Check Setup

38 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningThe Setup Login dialog box appears. Press .3. Enter the User

Strona 33

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 39Commissioning Chapter 3For the simulation tests, you only need to change two paramet

Strona 34

4 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Table of ContentsVerify E-Stop Functionality . . . . . . . . . . . . . . . . . . . .

Strona 35 - Control System Check

40 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press “0” on the keypad dialog and press .Parameter 007 w

Strona 36 - , press

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 41Commissioning Chapter 3Verify Operation of Frequency StepsThere are two parts to thi

Strona 37 - Access Setup Settings

42 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press , and press in the Start Drive? dialog box to con

Strona 38 - Set P Parameters

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 43Commissioning Chapter 35. Press and press in the Decel Speed by Step? dialog box

Strona 39 - Commissioning Chapter 3

44 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning2. Press to accept and begin the simulation.Actual Frequenc

Strona 40 - Chapter 3 Commissioning

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 45Commissioning Chapter 3Simulate Warnings and FaultsThis section describes how to sim

Strona 41 - Increase Frequency by Step

46 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press to view alarm record..4. Remove the jumper wires t

Strona 42

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 47Commissioning Chapter 36. Press , and press to confirm the operation in the Reset

Strona 43

48 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press to confirm the Transformer Cabinet Main Cooling Fa

Strona 44

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 49Commissioning Chapter 33. Press and confirm the Power Module Cabinet Fan Fault.4.

Strona 45 - Simulate Warnings and Faults

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 5Table of ContentsSpeed Reference Functions. . . . . . . . . . . . . . . . . . . . . .

Strona 46

50 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning5. Press to return to the Main Interface Screen. 6. Press

Strona 47

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 51Commissioning Chapter 36. Press to remove the fault. Press to confirm operation

Strona 48

52 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning6. Under Control Owner Selection, press .7. Select to conf

Strona 49

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 53Commissioning Chapter 32. Open the Bypass cabinet door, and close QS2 and QS3.Verify

Strona 50 - Verify E-Stop Functionality

54 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningBypass Isolation Switches1. Press from the Main Interface s

Strona 51

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 55Commissioning Chapter 33. Close the customer-supplied input circuit breaker by insta

Strona 52 - (Manual Bypass)

56 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning2. Close the customer-supplied input circuit breaker by insta

Strona 53

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 57Commissioning Chapter 3Verify the input and output drive contactors are closed.4. Pr

Strona 54 - Bypass Isolation Switches

58 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning5. Verify the input and output drive contactors are closed.By

Strona 55 - (Automatic Bypass)

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 59Commissioning Chapter 32. Press under Contactor Operation, and press to confirm..

Strona 56

6 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Table of ContentsNotes:

Strona 57 - , and press

60 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 Commissioning3. Press under Contactor Operation, and press to confirm..

Strona 58 - Bypass Contactors

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 61Commissioning Chapter 3Verify Operation of DCS Input and Output SignalsFigure 17 - S

Strona 59

62 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningWhen the two terminals specified are shorted, verify the resu

Strona 60

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 63Commissioning Chapter 3Press to enter password details. Press when finished.3. P

Strona 61 - Table 10 - 4-20 mA

64 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningSet Date and Time ZoneTo access the Date and Time Zone settin

Strona 62 - Restore P Parameter Settings

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 65Commissioning Chapter 3Change Time/Date/Regional Settings1. In Windows ME, press Ter

Strona 63

66 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 3 CommissioningNotes:

Strona 64 - Set Date and Time Zone

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 67Chapter 4No-load TestIntroductionNo-load TestThe No-load Test consists of the follow

Strona 65

68 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load TestEnergize Drive Control CircuitThe “Energize Control Circuit” p

Strona 66

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 69No-load Test Chapter 4P091 Skip Frequency 1 Upper Limit 0 ON 0 75 R&DP092 Skip F

Strona 67 - No-load Test

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 7PrefaceIntroductionThis document provides procedural information for commissioning Po

Strona 68 - Configure P and T Parameters

70 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load TestThere are no specific T parameters to modify when commissionin

Strona 69 - 0 ON -100 199.99 R&D

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 71No-load Test Chapter 4Parameters T11...T13To change Parameter T11:1. Press the T11 P

Strona 70 - (2) With Remote DCS only

72 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load Test2. In the Switch Method Selection dialog, press or . 3. If

Strona 71 - Parameters T11...T13

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 73No-load Test Chapter 4Change Parameter T12:1. Press the T12 Parameter input field.2.

Strona 72 - Chapter 4 No-load Test

74 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load TestChange Parameter T13:1. Press the T13 Parameter input field.2.

Strona 73 - 3. Press to accept

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 75No-load Test Chapter 4Close Isolation Switches in Bypass Cabinet1. Manual bypass (se

Strona 74

76 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load TestOperate Motor by HMI1. From the Main Interface Screen, press t

Strona 75 - Check Cooling Fan Operation

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 77No-load Test Chapter 43. Press , and press in the Start Drive? dialog box to conf

Strona 76 - Operate Motor by HMI

78 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load Test5. From the Main Interface Screen, press the Set Frequency: in

Strona 77 - No-load Test Chapter 4

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 79No-load Test Chapter 47. Press , and press in the Start Drive? dialog box to conf

Strona 78 - Press to confirm

8 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014PrefaceIf the drawings require changes to suit the installation and application of th

Strona 79

80 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Chapter 4 No-load Test13. Switch on the customer-supplied control power, and push th

Strona 80 - Load Test of Drive System

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 81Appendix ATorque RequirementsTorque RequirementsProper tightening torque must be use

Strona 81 - Torque Requirements

82 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix A Torque RequirementsNotes:

Strona 82

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 83Appendix BSingle Line DiagramsFigure 18 - PowerFlex 6000 without BypassQFInput Circu

Strona 83 - Single Line Diagrams

84 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix B Single Line DiagramsFigure 19 - 6012M Automatic Bypass Version 1 (without

Strona 84

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 85Single Line Diagrams Appendix BFigure 20 - 6012M Automatic Bypass Version 2 (with Is

Strona 85

86 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix B Single Line DiagramsFigure 21 - 6012M Manual BypassQFInput Circuit Breake

Strona 86

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 87Appendix CSpecial Function Parameter SettingsOverviewTable 12 on page 68 outlines sp

Strona 87 - System Setting Functions

88 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix C Special Function Parameter SettingsSwitch Control SourcesRelevant paramet

Strona 88 - Motor Parameter Setting

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 89Special Function Parameter Settings Appendix CAnalog Output Display Parameter Settin

Strona 89 - Restore Factory Setting

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 9PrefaceGeneral PrecautionsAdditional ResourcesThese documents contain additional info

Strona 90 - Speed Command Functions

90 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix C Special Function Parameter SettingsSpeed Command FunctionsSet Frequency C

Strona 91 - Frequency Skip

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 91Special Function Parameter Settings Appendix CFrequency Amplitude LimitRelevant para

Strona 92 - Speed Reference Functions

92 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix C Special Function Parameter SettingsSpeed Reference FunctionsV/F Curve Set

Strona 93 - Flying Start Function

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 93Special Function Parameter Settings Appendix CAnalog InputRelevant parameter: P205,

Strona 94 - Restart the Drive

94 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014Appendix C Special Function Parameter SettingsSome parameters must be changed based

Strona 95

Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 95IndexAAnalog Input 93CCabinet PlatesPre-Commissioning Sealing 29Commissioning 31Cont

Strona 96

96 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014IndexMechanical Inspection 21Interconnection Review 20Checklist 20Software 15Test Eq

Strona 98 - Documentation Feedback

Publication 6000-IN007A-EN-P - October 2014 - Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in Canada.Rockwell Automati