Rockwell-automation 22-COMM-B PowerFlex BACnet MS/TP Adapter Instrukcja Użytkownika Strona 28

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 27
2-12 Installing the Adapter
5. Insert the 3-pin linear plug into the mating adapter socket.
6. Close or install the drive cover.
7. Apply power to the drive.
8. Verify that adapter Parameter 07 - [Baud Rate Act] is reporting the
actual network baud rate. If not, use Parameter 06 - [Baud Rate
Cfg] to set the adapter to a fixed baud rate that matches the network
baud rate.
TIP: After the drive is connected and communicating on the BACnet
MS/TP network, it may be necessary to set additional adapter parameters
to meet your application requirements (for example Parameters 02 -
[Comm Loss Action] or 03 - [Comm Loss Time]).
For instructions to use an optional PowerFlex 4-Class HIM to access
adapter parameters, see Using the Optional, External PowerFlex 4-Class
HIM on page 3-2.
Przeglądanie stron 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 71 72

Komentarze do niniejszej Instrukcji

Brak uwag