
Using BACnet Objects 4-5
Table 4.A BACnet Object Descriptions and Supported Drives (Continued)
Object Name Use This Object to…
Compatible PowerFlex Drives
4 4M 40 400
BI1 Start Input Read the state of the Start Input on the drive’s I/O terminal block. ✔✔✔✔
BI2 Dir Input Read the state of the Dir (Direction) Input on the drive’s I/O terminal block. ✔✔✔✔
BI3 Digital Input 1 Read the state of Digital Input 1 on the drive’s I/O terminal block. ✔✔✔✔
BI4 Digital Input 2 Read the state of Digital Input 2 on the drive’s I/O terminal block. ✔✔✔✔
BI5 Digital Input 3 Read the state of Digital Input 3 on the drive’s I/O terminal block. — — ✔✔
BI6 Digital Input 4 Read the state of Digital Input 4 on the drive’s I/O terminal block. — — ✔✔
Binary Output (BO) Objects
BO0 Digital Output Cmd 1 Read/write the state of Digital Output 1 on the drive’s I/O terminal block. The
drive must be configured to accept the value of this output from the network.
This is done by setting the following drive parameter:
• PowerFlex 4/40: P055 - [Relay Out Sel] to the value “20” (ParamControl)
• PowerFlex 4M: t221 - [Relay Out Sel] to the value “11” (ParamControl)
• PowerFlex 400: T055 - [Relay Out1 Sel] to the value “12” (ParamControl)
✔✔✔✔
BO1 Digital Output Cmd 2 Read/write the state of Digital Output 2 on the drive’s I/O terminal block. The
drive must be configured to accept the value of this output from the network.
This is done by setting the following drive parameter:
• PowerFlex 40: P058 - [Opto Out1 Sel] to the value “20” (ParamControl)
• PowerFlex 400: T060 - [Relay Out2 Sel] to the value “12” (ParamControl)
——✔✔
BO2 Digital Output Cmd 3 Read/write the state of Digital Output 3 on the drive’s I/O terminal block. The
drive must be configured to accept the value of this output from the network.
This is done by setting the following drive parameter:
• PowerFlex 40: P061 - [Opto Out2 Sel] to the value “20” (ParamControl)
• PowerFlex 400: T065 - [Opto Out Sel] to the value “12” (ParamControl)
——✔✔
Komentarze do niniejszej Instrukcji