Rockwell-automation 25-COMM-P PowerFlex PROFIBUS DPV1 Adapter Instrukcja Użytkownika Strona 9

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 8
Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013 9
Getting Started Chapter 1
Yo u c a n v i e w a dap te r Device parameters and Host parameters with any of the
following drive configuration tools:
PowerFlex 520-series drive built-in keypad
PowerFlex 22-HIM-A3 or 22-HIM-C2S HIM
Connected Components Workbench software – click the tab for the
adapter at the bottom of the window, and click the Parameters icon in the
tool bar.
Compatible Products
At the time of publication, the adapter is compatible with the following:
PowerFlex 523 drives (all firmware revisions)
PowerFlex 525 drives (all firmware revisions)
Required Equipment
Equipment Shipped with the Adapter
When you unpack the adapter, verify that the package includes the following:
User-Supplied Equipment
The Device and Host parameters can be configured using the PowerFlex 520-
series drive built-in keypad (see Using the Drive Keypad Interface to Access
Parameters on page 23). In addition, you must supply:
One PowerFlex 25-COMM-P PROFIBUS DPV1 adapter
(installed in a PowerFlex 520-series drive control module back cover)
Two interface connectors
(one for connecting the adapter to PowerFlex 523 drives, one for connecting the adapter to PowerFlex 525 drives)
One Installation Instructions leaflet, publication 520COM-IN001
A small screwdriver
PROFIBUS cable; only use cable that conforms to PROFIBUS cable standards
(Belden #3079A PROFIBUS cable or equivalent is recommended)
One 9-pin, male D-Sub PROFIBUS connector
PROFIBUS connectors are available from a variety of sources and in various sizes. As such, there may be mechanical
limitations that prohibit the use of some connectors. Phoenix SUBCON-PLUS-PROFIB/AX/SC (Part # 2744380),
Siemens 6GK1500-0FC00, or Brad BM5G60PP4Mxxx are recommended for use with PowerFlex 520-series drives.
Configuration tool, such as the following:
PowerFlex 22-HIM-A3 or 22-HIM-C2S HIM
Connected Components Workbench (version 3 or greater)
Connected Components Workbench is the recommended stand-alone software tool for use with PowerFlex
drives. You can obtain a free copy by downloading it or requesting a DVD. Both options are available at
http://ab.rockwellautomation.com/Programmable-Controllers/Connected-Components-Workbench-Software
.
Controller configuration software RSLogix 5000 (version 20 or greater) or Logix Designer (version 21 or greater)