5-45
Faulted State for Digital Outputs
A digital output channel is faulted (the state reports a value of 7) when normal
operation or diagnostics tests have identified a specific fault condition. A single
identified fault condition thus results in a state value of 7.
When the state reports the value 7 then the following 'safe' values are reported by the
other variables:
Line Fault = TRUE
Discrepancy = TRUE
Channel Fault = TRUE
Voltage = 0mV
Current = 0mA
Configure Advanced Channel Settings for Digital Outputs
The AADvance Workbench provides advanced settings for individual digital output
channels:
You can specify a shutdown state for an output; this defines how the output will
behave when its parent 9451 digital output module is in a shutdown mode.
You can disable the line test feature for an output; this disables detection of a no-
load condition.
To configure the advanced channel settings do the following:
1) Select a slot with a digital output module.
The module status variable name <tagname> that you assigned appears in the
Variable field.
2) Select Channel 01 and click the Advanced tab.
The 9451 Advanced Channel Settings dialog box opens.
3) Put a tick in the box labelled Use Custom Advanced Channel Settings.
4) Select the Shutdown State row and then select an option from the pull down list