Processor Module B Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = The 9110 processor module in the given slot is healthy and its Healthy
LED indicator is green.
FALSE = The processor module is faulty and its Healthy LED indicator is red.
Description:
Reports the health status of a processor module.
Processor Module C Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = The 9110 processor module in the given slot is healthy and its Healthy
LED indicator is green.
FALSE = The processor module is faulty and its Healthy LED indicator is red.
Description:
Reports the health status of a processor module.
Processor Module A 24V1 Power Feed Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = power feed voltage is within specification (18 to 32V dc).
FALSE = power feed is outside specification.
Description:
Reports the health of power feed 1 (nominal 24V dc) to the 9110 processor module in
the given slot.
Processor Module B 24V1 Power Feed Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = power feed voltage is within specification (18 to 32V dc).
FALSE = power feed is outside specification.
Description:
Reports the health of power feed 1 (nominal 24V dc) to the 9110 processor module in
the given slot.
Processor Module C 24V1 Power Feed Health