Rockwell-automation AADvance Controller Configuration Guide Instrukcja Użytkownika Strona 244

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 286
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 243
10-10
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
00
3) Select the Network tab and enter the values; the default recommended values:
Connect TimeOut = 1000
BindResp Timeout = 1200
MaxAge = 2500
BindReqTimeout = 1000
Update Timeout = 60000
Configure Bindings
You need to set up data links between resources to create binding variables. You can
link resources from the Internal Bindings List Window or set up a link between
resources from the Link Architecture view.
1) Select the Link Architecture View.
2) Select the data link button on Resource 1 and extend the data line to the data
link button on Resource 2.
3) Repeat this for Resource 2 to Resource 1.
Przeglądanie stron 243
1 2 ... 239 240 241 242 243 244 245 246 247 248 249 ... 285 286

Komentarze do niniejszej Instrukcji

Brak uwag