Rockwell-automation AADvance Controller Configuration Guide Instrukcja Użytkownika Strona 197

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 286
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 196
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
9-11
Connect a Slave Device, Full Duplex
You can use a full duplex serial connection to connect a single Modbus slave device to
the AADvance controller. To make the physical connection, do the following:
1) Select a suitable cable. We recommend 3-pair, overall shielded cable.
2) Remove the serial port connector from the 9100 processor base unit.
3) Make the connections shown in the illustration. Terminate the twisted pairs with a
120 resistor in series with a 68nF capacitor at the receiver ends.
4) Connect the signal ground (not illustrated) from the 0V terminal to the slave
device.
Note: Do not connect the signal ground to the AC safety ground.
5) Insert the connector into the 9100 processor base unit.
Przeglądanie stron 196
1 2 ... 192 193 194 195 196 197 198 199 200 201 202 ... 285 286

Komentarze do niniejszej Instrukcji

Brak uwag