Configuration Guide (AADvance Controller)
Modbus Slave Link Identification and Control Settings
Each Modbus slave link object has a set of identification and control settings as detailed
in the tables.
Note: The AADvance Workbench groups these settings together under the label
'General'.
Table 29: Modbus RTU Slave Link Identification and Control Settings
You have to allocate a unique Slave Id
for each slave configured to a
particular master
Used in conjunction with the master
message timeout value
1 to 65,536,
or 0 to disable
The address of a control register (†)
0 = inactive
1 = standby
2 = active
1 to 65,536,
or 0 to disable
The address of a status register (†)
0 = healthy
1 = initializing
2 = communications failure
3 = error
Do Not Ping;
Function Code 08;
Read Holding Register
1 to 65,536,
or 0 to disable
Note: (†) The 'remarks' here summarize the values allowed for the contents of the
register. The Control variable may be written to by the application to switch the state
of the slave. The Status variable may be read by the application to monitor the slave.
These variables are described in Modbus Slave Link Control and Status Registers.