Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
At the beginning of a connection or
following "BindRespTimeout" milliseconds
during data exchange.
Producer and consumer binding tables
CRC mismatch during connection
SNCP_KVB_ERR_IMPOSSIBLE_TO_
BIND
Conversion of structures not supported on
hetrogeneous binding link
Producer only error, indicates that a
consumer with an unknown/unexpected IP
Address is requesting a bindings link. The
link is denied.
SNCP_KVB_ERR_BAD_PRODUCER_
ID
Producer only error, indicates that the
producer has received a bindings link
request from a consumer and that request
does not contain the expected producer
identity. The link is denied.
SNCP_KVB_ERR_BAD_GROUP_ID
Producer only error, indicates that the
producer has received a bindings link
request from a consumer, and that request
does not contain a known bound variable
group identity. The link is denied.
SNCP_KVB_ERR_BAD_BUFF_SIZE
Producer only error, indicates that either
the producer or consumer does not have
sufficient buffer space to translate the
bound variables so that the link cannot be
established.
Producer only error, indicates that the
producer is unable to obtain the consumers
IP address information from the network
configuration file. The link is denied.