Rockwell-automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Instrukcja Użytkownika Strona 101

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 168
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 100
DeviceNet Adapter Parameters
B-9
Master-slave output data. This data is produced by the adapter and
consumed by the scanner.
Mask of the 16-bit Logic Status word. Unless they are masked out,
the bits in the Logic Status word are checked for changes when the
adapter is allocated using COS (change of state). If a bit changes, it
is reported as a change in the change of state operation. If the mask
bit is 0 (Off), the bit is ignored. If the mask bit is 1 (On), the bit the
checked.
Important: The bit definitions in the Logic Status word depend on
the drive.
Hysteresis band to determine how much the Feedback word can
change before it is reported as a change in the COS (change of
state) operation.
26 M-S Output
Range:
0 = I/O Disabled
1 = I/O Enabled
Default:
See figure B.4.
Type:
Read/Write
Reset Required:
Yes
Figure B.4 – M-S Output (26)
00010xxx
01234567
1=I/O Enabled
0=I/O Disabled
x =Not Used
Status/Fdbk
DL A Input
DL B Input
DL C Input
DL D Input
Not Used
Not Used
Not Used
27 COS Status Mask
Range:
0 = Off
1 = On
Default:
0000 0000 0000 0000
Type:
Read/Write
Reset Required:
No
28 COS Fdbk Change
Range:
0 to 4294967295
Default:
0
Type:
Read/Write
Reset Required:
No
Przeglądanie stron 100
1 2 ... 96 97 98 99 100 101 102 103 104 105 106 ... 167 168

Komentarze do niniejszej Instrukcji

Brak uwag