Rockwell-automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Instrukcja Użytkownika Strona 64

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 168
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 63
6-10
DeviceNet Adapter for use with DPI AC Drives
Figure 6.6 – Sample PLC-5 Ladder Logic Program (continued)
0007
12
N10:1
2
SP600
JOG
Command Bit
0008
13
N10:1
3
SP600
CLEAR FAULT
Command Bit
0009
MOV
Move
Source N21:0
0<
Dest N10:2
0<
SP600
REFERENCE
Command Word
0010
BT20:1
EN
EN
DN
ER
BTW
0011
END
Operator Input
Drive Jog
Command Bit
Operator Input
Drive Clear Faults
Command Bit
I:000
I:000
Block Transfer Write
Module Type Generic Block Transfer
Rack 000
Group 0
Module 0
Control Block BT20:1
Data File N10:0
Length 62
Continuous No
11
N10:1
0
SP600
STOP
Command Bit
Operator Input
Drive Stop
Command Bit
I:000
0006
The Block Transfer Write in this rung sends
the drive command to the scanner and out to
the drive via the DeviceNet network.
Przeglądanie stron 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 167 168

Komentarze do niniejszej Instrukcji

Brak uwag