Configuring the Scanner
5-7
In our example, we are using a 1747-SDN and selected Discrete.
Step 3. In the Start Word box, select the word in memory at which
the data should start. In our example, we selected 1. Logic
Status and Speed Feedback information will be found in
I:1.1 and I:1.2, respectively.
5.3.2 Mapping the Output I/O
Step 1. In the Scanner Module dialog box, click the
Output
tab.
See figure 5.6. To display this dialog box, right-click the
scanner in the configuration view (figure 5.2).
If you selected the
Automap on Add
box in the Scanlist page
(figure 5.3), RSNetWorx has already mapped the I/O. If it is not
mapped, click
Automap
to map it. If you need to change the
mapping, click
Advanced
and change the settings. Click
Help
for
assistance.
Table 5.4 – Scanner Module Memory Locations
Scanner Memory Locations
1747-SDN Discrete or M-File
1756-DNB Assembly Data
1771-SDN Block Xfer 62 – 57
Figure 5.6 – Output Page on the Scanner Module Dialog Box