5-8
DeviceNet Adapter for use with DPI AC Drives
Step 2. In the Memory box, select a location in scanner memory
from table 5.5.
In our example, we are using a 1747-SDN scanner and selected
Discrete.
Step 3. In the Start Word box, select the word in memory at which
the data should start. In our example, we selected 1. Logic
Command and Speed Reference data should be written to
O:1.1 and O:1.2, respectively.
5.4 Saving the Configuration
After configuring a scanner, you must download it to the scanner.
You should also save it to a file on your computer.
Step 1. In the Scanner Module dialog box (figure 5.6), click
Apply
to save the configuration to the scanner. A Scanner
Configuration Applet appears and asks if it is OK to
download the changes.
Step 2. Click
Yes
to download the changes. The changes are
downloaded and then the Scanner Module dialog box
reappears.
Step 3. Click
OK
to close the Scanner Module dialog box.
Step 4. Select
File > Save
. If this is the first time that you saved
the project, the Save As dialog box appears. Navigate to a
folder, type a file name, and click
Save
to save the
configuration to a file.
Table 5.5 – Scanner Module Memory Locations
Scanner Memory Locations
1747-SDN Discrete or M-File
1756-DNB Assembly Data
1771-SDN Block Xfer 62 – 57