Troubleshooting the DeviceNet Adapter and Network
8-3
8.1.2 MS Status Indicator
Table 8.2 – MS Status Indicator: State Definitions
State Cause Corrective Action
Off The adapter is not
powered.
Securely connect the
adapter to the drive using the
ribbon cable.
Apply power to the drive.
Flashing
Red
The adapter has failed
the firmware test or
the node address
switch setting is
invalid.
Verify that the node address
switch setting is between 0
and 63.
Clear faults in the adapter.
Cycle power to the drive.
If cycling power does not
correct the problem, the
parameter settings may have
been corrupted. Reset
defaults and reconfigure the
adapter.
If resetting defaults does not
correct the problem, flash the
adapter with the latest
firmware release.
Solid
Red
The adapter has failed
the hardware test.
Cycle power to the drive.
Replace the adapter.
Flashing
Green
The adapter is
operational, but is not
transferring I/O data.
Place the scanner in RUN
mode.
Program the controller to
recognize and transmit I/O to
the adapter.
Configure the adapter for the
program in the controller.
Solid
Green
The adapter is
operational and
transferring I/O data.
No action.