C-26
DeviceNet Adapter for use with DPI AC Drives
Response Data for Get_Attributes_Scattered
Format for Set_Attributes_Scattered Service
The structure shown below can get up to eight parameters in a
single message. In the Response Message, a parameter number
with the high bit set indicates that the associated pad word field
contains an error code.
Address
Value
(hex) Description Refer To . . .
N30:70 0101 TXID = 01, Status = 01 (successful transaction) Section 7.3
N30:71 0012 Port = 00, Size = 18 bytes (12 hex) Section 7.3
N30:72 CB01 Service = CB (successful) Section 7.3
Address = 01 (Node Address) Section 7.3
N30:73 0001 Parameter Number 1
N30:74 0258 Value = 600 (258 hex) = 60.0 Hz
N30:75 0000
N30:76 0003 Parameter Number 3
N30:77 0001 Value = 1 (1 hex) = 0.1A
N30:78 0000
N30:79 0006 Parameter Number 6
N30:80 0864 Value = 2148 (864 hex) = 214.8V AC
N30:81 0000
Request Response
Word 0 TXID Command TXID Status
1 Port Size Port Size
2 Service Address Service Address
3 Class Parameter Number
4 Instance Pad Word or Error Code
5 Attribute Pad Word
6 Parameter Number Parameter Number
7 Parameter Value LSW Pad Word or Error Code
8 Parameter Value MSW Pad Word
9 Parameter Number Parameter Number
10 Parameter Value LSW Pad Word or Error Code
11 Parameter Value MSW Pad Word