7-20 Pico GFX Control Commands
Read/write function block
data
Always note the following when working with function blocks:
The relevant data is transferred in Intel format. In other words,
the first byte is the low byte (Byte 4) and the last byte (byte 7)
the high byte.
The maximum data length is 4 bytes. All values must be
transferred in hexadecimal format.
All 32-bit values are treated as signed values. When transferring
32-bit values, ensure that the appropriate value range is suitable
for long integers, i.e. signed.
32-bit value: –2147483648 .. 0 .. +2147483647
For SN1 – SN32: 0A For SN1 – SN32: 0A
2 3 Index
01 – 08
(1)
01 – 08
(1)
3 – 6 4 – 7 Data 1 – 4 00 Table 6.97
(1) Corresponds to NET-ID
Table 6.97 Byte 4 to 7: Data 1 to 4
Data 1 Bit76543210
RN1 SN1 ... 0/1
... 0/1
RN8 SN8 0/1
Data 2 Bit76543210
RN9 SN9 0/1
.... ...
RN16 SN16 0/1
Data 3 Bit76543210
RN17 SN17 0/1
... ...
RN24 SN24 0/1
Data 4 Bit76543210
RN25 SN25 0/1
... ...
RN32 SN32 0/1
Table 6.96
Byte Meaning Value (hex), sent by
Master Slave Master Slave