Rockwell-automation 1760-DNET Pico DeviceNet Communications Module Use Instrukcja Użytkownika Strona 149

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 168
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 148
1 Publication 1760-UM003A-EN-P - September 2005
Chapter
A
Specifications
Technical Data
Table 1.1 General Specifications
Description Specification
Standards and regulations EN 61000-6-1; EN 61000-6-2; EN 61000-6-3;
EN 61000-6-4, IEC 60068-2-27, IEC 50178
Dimensions W x H x D 35.5 x 90 x 56.5 mm
Weight 150 g
Mounting DIN 50022 rail, 35 mm screw fixing with
fixing bracket ZB4-101-GF1 (accessories)
Table 1.2 Climatic environmental conditions (Cold to IEC 60068-2-1, Heat to IEC
60068-2-2)
Description Specification
Ambient temperature Installed
horizontally/vertically
–25 to +55 °C
Condensation Prevent condensation with suitable
measures
Storage/transport temperature –40 to +70 °C
Relative humidity (IEC 60068-2-30), no
moisture condensation
5 to 95 %
Air pressure (operation) 795 to 1080 hPa
Corrosion resistance (IEC 60068-2-42, IEC
60068-2-43)
SO2 10 cm3 /m3, 4 days
H2S 1 cm3 /m3, 4 days
Table A.3 Mechanical Ambient Conditions
Description Specification
Pollution degree 2
Degree of protection (EN 50178, IEC 60529,
VBG4)
IP20
Vibration (IEC 60068-2-6)
constant amplitude 0.15 mm
10 to 57 Hz
Vibration (IEC 60068-2-6)
constant acceleration 2 g
57 to 150 Hz